Home > Products > Heat Pump for Heating, Cooling and DHW > R290 DC Inverter heat pump > R290 DC Inverter Heat Pump for Heating, Cooling and DHW
  • R290 DC Inverter Heat Pump for Heating, Cooling and DHW

R290 DC Inverter Heat Pump for Heating, Cooling and DHW

Product Description

R290 DC inverter heat pump is a new energy-saving solution which uses environmentally friendly R290 refrigerant and full DC inverter technology to heat, cool and to produce domestic hot water.

 

R290 DC Inverter Heat Pump for Heating, Cooling and DHW

 

Features of R290 DC Inverter Heat Pump

 

R290 Refrigerant

R290 refrigerant is a naturally occurring refrigerant, making it environmentally friendly, it has zero Ozone Depletion Potential (ODP=0), meaning it doesn’t contribute to the depletion of the ozone layer; And it has a low Global Warming Potential (GWP=3), meaning it doesn’t contribute significantly to global warming. It is the perfect solution for renovations, where a high water outlet temperature is required.

 

R290 DC Inverter Heat Pump for Heating, Cooling and DHW

 

Full DC Inverter Technology

Guangteng heat pump with R290 refrigerant is the real full inverter heat pump by DC inverter compressor, DC inverter control system and DC inverter fan motor. Inverter technology makes it possible to automatically adapt the compressor and fan rotation speed to the house heating needs and to weather conditions. 

 

DC Inverter Technology

 

High Efficiency A+++ Energy Class

Guangteng R290 DC inverter heat pumps are tested by TUV, achieving the ERP A+++ energy class, the highest energy efficiency.

 

R290 DC Inverter Heat Pump for Heating, Cooling and DHW

 

Smart WiFi Control

With smart WiFi APP control, you can check or control your heat pump anytime, anywhere easily.

 

R290 DC Inverter Heat Pump for Heating, Cooling and DHW

 

Touch Display

 

R290 DC Inverter Heat Pump for Heating, Cooling and DHW

 

If you want to know more information about R290 DC inverter heat pump, please contact us. We will provide professional answers.

 

contact us

 

Technical Data of R290 DC Inverter Heat Pump

Model number GT-SKR020KBDC-M290 GT-SKR030KBDC-M290 GT-SKR040KBDC-M290 GT-SKR040KBDC-M290T GT-SKR050KBDC-M290T
Heating at A7/W35
Heating capacity (min~max) KW 6.40 (2.83~8.00) 8.30 (3.65~10.38) 11.60 (5.10~14.50) 12.00 (5.28~15.00) 16.30 (8.80~21.20)
Power input (min~max) KW 1.47 (0.65~1.84) 1.93 (0.85~2.42) 2.75 (1.21~3.44) 2.90 (1.28~3.63) 3.69 (1.99-4.80)
COP  W/W 4.34 (3.03~5.21) 4.30 (3.01~5.16) 4.22 (3.03~5.10) 4.15 (3.0~5.0) 4.42 (3.1~5.3)
Heating at A2/W35
Heating capacity (min~max) KW 5.80 (2.55~7.25) 7.11 (3.13~8.89) 10.43 (4.59~13.04) 10.30 (4.53~12.88) 14.31 (6.86~18.60)
Power input  (min~max) KW 1.60 (0.71~2.00) 2.06 (0.91~258) 2.76 (1.22~3.45) 2.85 (1.25~3.56) 3.67 (1.98~4.84)
COP W/W 3.60 (2.52-4.32) 3.45 (2.48~4.30) 3.78 (2.65~4.54) 3.61 (2.53~4.40) 3.90 (2.73~4.68)
Heating at A7/W55
Heating capacity (min~max) KW 5.75 (2.53~7.19) 7.70 (3.40~9.63) 11.08 (4.88~13.85) 11.43 (5.03~14.29) 14.71 (7.94~19.13)
Power input (min~max) KW 2.03 (0.89~2.54) 2.70 (1.19~3.38) 3.82 (1.68~4.78) 4.07 (1.79~5.09) 5.02 (2.71~6.53)
COP  W/W 2.83 (2.3-3.8) 2.85 (2.00-3.42) 2.90 (2.03-3.48) 2.81 (2.02-3.41) 2.93 (2.05-3.52)
Heating at A2/W55
Heating capacity (min~max) KW 5.14 (2.27~6.43) 6.72 (2.96~8.40) 9.61 (4.23~12.00) 9.70 (4.59~12.63) 13.81 (7.45~17.95)
 Power input  (min~max) KW 2.06 (0.91~2.58) 2.71 (1.20~3.39) 3.74 (1.65~4.68) 3.99 (1.76~4.84) 4.93 (2.66~6.41)
COP W/W 2.45 (2.0-3.45) 2.48 (2.0-3.6) 2.57 (2.2-3.7) 2.43 (2.0-3.6) 2.80 (2.2-3.9)
 
Cooling at A35/W7
Cooling capacity (min~max) KW 3.70 (2.22~5.92) 6.20 (3.40~8.10) 9.30 (5.15~12.09) 9.50 (5.22~12.35) 13.30 (7.10~17.3)
power input (min~max) KW 1.32 (0.79~2.11) 2.20 (1.21~2.86) 3.25 (1.76~4.16) 3.28 (1.79~4.20) 4.60 (2.53~5.98)
EER W/W 2.80 (2.02-3.36) 2.80 (2.00-3.42) 2.85 (2.05-3.42) 2.80 (2.00-3.50) 2.90 (2.10-3.48)
SCOP
SCOP (TWW for 35°C class)  N/A 4.47 4.49 4.59  4.63  4.51 
Energy lable(TWW at 35°C) N/A A+++ A+++ A+++ A+++ A+++
SCOP (TWW for 55°C class)  N/A 3.59  3.58  3.67  3.60  3.62 
Energy lable(TWW at 55°C) N/A A++ A++ A++ A++ A++
 
Power supply V/Ph 220~240/1/50 220~240/1/50 220~240/1/50 380~415/3N/50 380~415/3N/50
Compressor N/A DC Inverter DC Inverter DC Inverter DC Inverter  DC Inverter
Fan motor N/A DC DC  DC DC DC
Fan motor qty pc 1 1 2 2 2
Water circulation pump N/A Inverter Inverter Inverter Inverter Inverter
Refrigerant N/A R290 / 700g R290 / 1100g R290 / 1200g R290 / 1200g R290 / 1600g
CO2 equivalent T 0.0021 0.0033 0.0036 0.0036 0.0048
Refrigerant regulation N/A Electronic expansion valve
Heat exchanger type N/A Brazed plate heat exchanger
Water connection Inch 1 1 1 1 1
Norminal water flow m3/h 1.4 1.8 2.7 2.7 3.6
Operating outdoor temp -25~43 -25~43 -25~43 -25~43 -25~43
Max heating water temp 75 75 75 75 75
Min cooling water temp 10 10 10 10 10
Sound level dB(A) 60 63 67 67 73
Degree of protection N/A IPX4 IPX4 IPX4 IPX4 IPX4
Net weight  kg 80 85 99 99 135
Dimension mm 1100*460*795 1100*460*795 1115*470*1020 1115*470*1020 1165*470*1280

 

Test condition:                

1. A7/W35: outdoor air temperature 7℃ DB/6℃ WB, water inlet/outlet temperature 30℃/35℃                
2. A2/W35: outdoor air temperature 2℃ DB/1℃ WB, water inlet/outlet temperature 30℃/35℃                
3. A7/W55: outdoor air temperature 7℃ DB/6℃ WB, water inlet/outlet temperature 47℃/55℃                
4. A2/W55: outdoor air temperature 2℃ DB/1℃ WB, water inlet/outlet temperature 47℃/55℃                
5. A35/W7: outdoor air temperature 35℃ , water inlet/outlet temperature 12℃/7℃

 

Contact Us
  • E-mail: kelly@guangteng.com
  • Tel.: +86 137 9463 3636
  • Add.: Building 2, Jilong Zhizao Industrial Park, No. 52 Xilian Road, Leliu, Shunde, Foshan 528322, Guangdong, China